Hager MBN110 is a modular circuit breaker designed to protect AC electrical circuits against overload and short circuit conditions. With one protected pole and a rated current of 10 A, it is suitable for single-phase lighting circuits, socket groups, and individual loads in residential, administrative, and other low-voltage installations. The device is rated for 400 V AC and operates at a frequency of 50–60 Hz, making it appropriate for standard distribution boards used in everyday electrical systems.
The tripping characteristic B indicates use in circuits with low inrush currents, which is typically required for lighting and other loads without significant start-up surges. The rated breaking capacity is 6 kA according to EN 60898 at 230 V, and the Icu value is also 6 kA according to IEC 60947-2 at 230 V. This means the breaker can interrupt fault currents within the declared standard limits. The current limiting class 3 helps reduce the thermal and mechanical impact of short-circuit currents on the installation.
The breaker is intended for flush mounting and occupies 1 module, with an installation depth of 70 mm. This format makes it suitable for compact modular panels and for integration into standard DIN-rail distribution assemblies. Connection is possible with solid conductors from 1 to 35 mm² and stranded conductors from 1 to 25 mm², which provides flexibility when assembling or servicing wiring. The protection class IP20 confirms that the device is intended for installation inside electrical enclosures rather than in exposed locations.
Additional electrical parameters include insulation voltage Ui of 500 V, impulse withstand voltage Uimp of 4 kV, pollution degree 2, and overvoltage category 3. The operating temperature range from -25 to +70 °C allows use in a wide range of indoor conditions. Power loss is 2.75 W. The breaker has no neutral switching, no explosion-proof construction, and no provision for additional accessories, so its function remains focused on basic overcurrent and short-circuit protection in modular low-voltage circuits.